FUJI Electric TR overload for SC series contactor
Product: FUJI TR Overload catalogue
TR Overload Selection Table
For use with: | Order code | min. | max. |
SC03 | TR-0N/3 0.1A | 0.1A | 0.15A |
SC-0 | TR-0N/3 0.13A | 0.13A | 0.2A |
SC-05 | TR-0N/3 0.15A | 0.15A | 0.24A |
TR-0N/3 0.2A | 0.2A | 0.3A | |
TR-0N/3 0.24A | 0.24A | 0.36A | |
TR-0N/3 0.3A | 0.3A | 0.45A | |
TR-0N/3 0.36A | 0.36A | 0.54A | |
TR-0N/3 0.48A | 0.48A | 0.72A | |
TR-0N/3 0.64A | 0.64A | 0.96A | |
TR-0N/3 0.8A | 0.8A | 1.2A | |
TR-0N/3 0.95A | 0.95A | 1.45A | |
TR-0N/3 1.4A | 1.4A | 2.2A | |
TR-0N/3 1.7A | 1.7A | 2.6A | |
TR-0N/3 2.2A | 2.2A | 3.4A | |
TR-0N/3 2.8A | 2.8A | 4.2A | |
TR-0N/3 4A | 4A | 6A | |
TR-0N/3 5A | 5A | 8A | |
TR-0N/3 6A | 6A | 9A | |
TR-0N/3 7A | 7A | 11A | |
SC-4-0 | TR-5-1N/3 4A | 4A | 6A |
SC-4-1 | TR-5-1N/3 5A | 5A | 8A |
SC-5-1 | TR-5-1N/3 6A | 6A | 9A |
TR-5-1N/3 7A | 7A | 11A | |
TR-5-1N/3 9A | 9A | 13A | |
TR-5-1N/3 12A | 12A | 18A | |
TR-5-1N/3 16A | 16A | 22A | |
SC-N1 | TR-N2/3 18A | 18A | 26A |
SC-N2 | TR-N2/3 24A | 24A | 36A |
TR-N2/3 32A | 32A | 42A | |
SC-N2S | TR-N3/3 34A | 34A | 50A |
SC-N3 | TR-N3/3 45A | 45A | 65A |
TR-N3/3 48A | 48A | 68A | |
TR-N3/3 53A | 53A | 80A | |
TR-N3/3 65A | 65A | 95A | |
TR-N3/3 85A | 85A | 105A | |
SC-N4 | TRN5/3 53A | 53A | 80A |
SC-N5A | TRN5/3 65A | 65A | 95A |
TRN5/3 85A | 85A | 105A | |
SC-N6 | TR-N6/3 85A | 85A | 125A |
TR-N6/3 110A | 110A | 160A | |
SC-N7 | TR-N7/3 110A | 110A | 160A |
SC-N8 | TR-N8/3 125A | 125A | 185A |
SC-N10 | TR-N10/3 160A | 160A | 240A |
FUJI TR Overload For SC series
HK$83.00Price
TR Overload for SC series Contactor
■ Features
● Manual trip- These relays can be manually tripped for sequence inspection by pressing manual trip bar (TR-0N/3, TR-5-1N/3).
- A sequence inspection will be performed when the test button is pulled out. When the test button is pressed in, only the NC contact will turn OFF. The original status will be restored when the test button is then released.(TR-N2/3 to N8/3)
● Trip-free mechanism
- Even if the reset button is carelessly pressed, this relay trips without trouble (Trip-free mechanism).
● Easy visual checking of perating status
- Trip indicator and manual trip bar permit visual check of tripping status.
● Dial ampe resetting
- The setting dial uses a RC (Rated Current) marking which is set to the motor full load current.